Omron SYSMAC CJ - REFERENCE MANUAL 08-2008 Reference Manual page 284

Programmable controllers
Hide thumbs Also See for SYSMAC CJ - REFERENCE MANUAL 08-2008:
Table of Contents

Advertisement

Timer and Counter Instructions
Basic Timer Specifications
Item
TIM/
TIMX(550)
Timing method
Decrement-
ing
Timing units
100 ms
Maximum SV
TIM: 999.9 s
TIMX:
6,553.5 s
Outputs/instruc-
1
tion
Timer numbers
Used
Completion Flag
At execution
refreshing
Timer PV
See note 1.
refreshing
(See note 5.)
Value
Com-
OFF
after
pletion
reset
Flags
PVs
SV
Timer Operation
Item
TIM/
TIMX(550)
Operating mode
PV = 0
change
Completion Flag = OFF
Power interrupt/reset
PV = 0
Completion Flag = OFF
Execution of
Binary: PV = FFFF, Completion Flag = OFF
CNR(545)/CNRX(547)
BCD: PV = FFFF or 9999, Completion Flag = OFF
Operation in jumped
Operating timers continue timing.
program section
(JMP(004)-JME(005))
Operation in inter-
PV = SV
locked program sec-
Completion Flag = OFF
tion (IL(002)-ILC(003))
Forced
Comple-
ON
set
tion Flag
PVs
Set to 0.
Forced
Comple-
OFF
reset
tion Flags
PVs
Reset to SV.
244
The following table shows the basic specifications of the timers.
TIMH(015)/
TMHH(540)/
TIMHX(551)
TMHHX(552)
Decrementing Decrementing Decrementing Decrementing Incrementing
10 ms
1 ms
TIMH: 99.99 s
TMHH:
9.999 s
TIMHX:
655.35 s
TMHHX:
65.535 s
1
1
Used
Used
At execution
At execution
See note 2.
Every 1 ms
At execution
OFF
OFF
SV
SV
Note
1. TIM PVs are refreshed at execution, at the end of program execution each
cycle, or every 80 ms by interrupt if the cycle time exceeds 80 ms.
2. TIMH(015)/TIMHX(551) PVs are refreshed at execution, at the end of pro-
gram execution each cycle, and every 10 ms by interrupt.
3. TIMU(541), TIMUX(556), TMUH(544), and TMUHX(557) are supported by
CJ1-H-R CPU Units only.
4. It is not possible to read the timer PVs of TIMU(541), TIMUX(556),
TMUH(544), and TMUHX(557).
5. Timers are refreshed at different times depending on the timer number.
Refer to the descriptions of individual timer instructions for details.
The following table shows the effects of operating and programming condi-
tions on the operation of the timers.
TIMH(015)/
TMHH(540)/
TIMHX(551)
TMHHX(552)
Note
1. TIMU(541), TIMUX(556), TMUH(544), and TMUHX(557) are supported by
CJ1-H-R CPU Units only.
TIMU(541)/
TMUH(544)/
TIMUX(556)
TMUHX(557)
(See note 3.)
(See note 3.)
0.1 ms
0.01 ms
TIMU:
TMUH:
0.9999 s
0.09999 s
TIMUX:
TMUHX:
6.5535 s
0.65535 s
1
1
Used
Used
At execution
At execution
At execution
At execution
OFF
OFF
--- (See note 4.)
TIMU(541)/
TMUH(544)/
TIMUX(556)
TMUHX(557)
--- (See note 2.)
--- (See note 2.)
Section 3-6
TTIM(087)/
TIML(542)/
TTIMX(555)
TIMLX(553)
Decrementing Incrementing
100 ms
100 ms
TTIM: 999.9 s
TIML:
115 days
TTIMX:
6,553.5 s
TIMLX:
49,710 days
1
1
Used
Not used
At execution
At execution
At execution
At execution
OFF
OFF
0
SV
TTIM(087)/
TIML(542)/
TTIMX(555)
TIMLX(553)
---
---
Not applica-
ble
Timer status is maintained.
Timer status
PV = SV
maintained.
Completion
Flag = OFF
---
Set to 0.
---
---
Set to 0.
---
MTIM(543)/
MTIMX(554)
100 ms
MTIM: 999.9 s
MTIMX:
6,553.5 s
8
Not used
At execution
At execution
OFF
0
MTIM(543)/
MTIMX(554)
---
---
Not applica-
ble
Timer sta-
tus main-
tained.
---
---
---
---

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac cs seriesSysmac one nsj seriesSysmac cj series

Table of Contents