Table Data Processing Instructions
Description
Area
Auxiliary Bit Area
Timer Area
Counter Area
DM Area
EM Area without bank
EM Area with bank
Indirect DM/EM
addresses in binary
Indirect DM/EM
addresses in BCD
Constants
Data Registers
Index Registers
Indirect addressing
using Index Registers
MIN(183) searches the range of memory from R1 to R1+C–1 for the minimum
value in the range and outputs that minimum value to D.
When bit 14 of C+1 has been set to 1, MIN(183) writes the PLC memory
address of the word containing the minimum value to IR00. (If two or more
words within the range contain the minimum value, the address of the first
word containing the minimum value is written to IR00.)
When bit 15 of C+1 has been set to 1, MIN(183) treats the data within the
range as signed binary data.
R1+(W–1)
Note MIN(183) can be processed in the background. Refer to the SYSMAC CS/CJ/
NSJ Series PLC Programming Manual (W394) for details.
C
A000 to A958
A000 to A959
T0000 to T4094
T0000 to T4095
C0000 to C4094
C0000 to C4095
D00000 to
D00000 to D32767
D32766
E00000 to
E00000 to E32767
E32766
En_00000 to
En_00000 to En_32767
En_32766
(n = 0 to C)
(n = 0 to C)
@ D0000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Specified values
---
only
---
---
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
PC memory
address
R1
C words
Min. value
Section 3-17
R1
D
A448 to A959
DR0 to DR15
W
C
733