Scaling: Scl(194) - Omron SYSMAC CJ - REFERENCE MANUAL 08-2008 Reference Manual

Programmable controllers
Hide thumbs Also See for SYSMAC CJ - REFERENCE MANUAL 08-2008:
Table of Contents

Advertisement

Data Control Instructions
000000
TPO
S
C
R

3-18-7 SCALING: SCL(194)

Purpose
Ladder Symbol
Variations
Applicable Program Areas
Operands
TPO(685) takes the duty ratio in D00010, converts
that duty ratio to a time-proportional output, and
D00010
Duty ratio
outputs the pulse output to bit 00 of CIO 0001.
D00000
Parameters
000100
Pulse output
D00000
1
1
0
0
0
6
D00001
D00002
0
7
D
D00003
1
F
4
D00004
Do not set.
D00005
Do not set.
D00006
Do not set.
:
:
D00010
0 to 2710 hex
Converts unsigned binary data into unsigned BCD data according to the
specified linear function.
SCL(194)
S
P1
R
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Block program
areas
OK
The contents of the four words starting with the first parameter word (P1) are
shown in the following diagram.
0
Duty ratio input, read initial value, and enable output limit function.
4
Control period = 1.00 s
0
Output lower limit = 20.00%
0
Output upper limit = 80.00%
0 to 100.00%
S: Source word
P1: First parameter word
R: Result word
Step program
areas
OK
OK
Section 3-18
SCL(194)
@SCL(194)
Not supported.
Subroutines
Interrupt tasks
OK
795

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac cs seriesSysmac one nsj seriesSysmac cj series