Omron SYSMAC CJ - REFERENCE MANUAL 08-2008 Reference Manual page 971

Programmable controllers
Hide thumbs Also See for SYSMAC CJ - REFERENCE MANUAL 08-2008:
Table of Contents

Advertisement

Basic I/O Unit Instructions
Purpose
Units Refreshed by
FIORF(225)
Flags
Precautions
The following table shows how FIORF(225) differs from IORF(097) and
DLNK(226).
Instruction
IORF(097)
• I/O refreshing of words used by Basic I/O Units
• I/O refreshing of the CIO words and DM words used by Special
FIORF(225)
• I/O refreshing of the CIO words and DM words used by a Spe-
DLNK(226)
• I/O refreshing of the CS1 CPU Bus Unit Area in the CIO Area
• I/O refreshing of the CS1 CPU Bus Unit Area in the DM Area
• Refreshing of data specific to the CPU Bus Unit, such as data
FIORF(225) and IORF(097) both refresh the words allocated to Special I/O
Units, but differ in the following ways.
• FIORF(225) has a faster instruction execution time.
• WIth FIORF(225), the relevant words are specified by the unit number
rather than word addresses.
A Special I/O Unit's regular cyclic I/O refreshing can be disabled in the PLC
Setup (by turning ON the Unit's Special I/O Unit Cyclic Refresh Disable Bit),
and I/O refreshing can be performed with the Unit only when necessary by
executing FIORF(225). This function allows a particular Special I/O Unit's data
to be refreshed when necessary, without increasing the cyclic I/O refreshing
time at other times.
Unit type (See note.)
Basic I/O Units
The following areas allocated to a Special I/O Unit
(The words allocated to the specified Unit are
refreshed together.)
• Allocated CIO Area words
• Allocated DM Area words
CPU Bus Units
Note This table applies to Units mounted in a CPU Rack or an Expansion Rack. It
does not apply to Units mounted in a SYSMAC Bus Slave Rack.
Name
Error Flag
ER
Equals Flag
=
I/O refreshing by FIORF(225) will be stopped if an I/O Bus Error occurs while
during I/O refreshing.
I/O Units
cial I/O Unit
(25 words)
(100 words)
link data or DeviceNet Remote I/O Communications data
Label
ON if the specified unit number is not between 0000 and
005F hex (between 0 and 95 decimal).
ON if the PLC does not have a Special I/O Unit with the
unit number specified by N.
ON if the specified Special I/O Unit uses more is allocated
words for two or more unit numbers, but the unit number
specified by N is not the lowest of those unit numbers.
OFF in all other cases.
ON if the I/O refreshing was completed normally.
OFF if FIORF(225) was executed while the specified Spe-
cial I/O Unit was being refreshed during cyclic refreshing.
Section 3-23
Operation
Refreshable by FIORF(255)
No
Yes
No
Operation
931