Double-precision Floating-point Instructions (CS1-H, CJ1-H, CJ1M, or CS1D Only)
Precautions

3-16-10 DOUBLE RADIANS TO DEGREES: DEGD(850)

Purpose
Ladder Symbol
Variations
Applicable Program Areas
Operand Specifications
The source data in words S to S+3 must be in IEEE754 floating-point data for-
mat.
Converts a double-precision (64-bit) floating-point number from radians to
degrees and places the result in the specified result words.
This instruction is supported by CS1-H, CJ1-H, CJ1M, and CS1D CPU Units
only.
DEGD(850)
S: First source word
S
D: First destination word
D
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Block program areas
OK
OK
Area
CIO Area
Work Area
Holding Bit Area
Auxiliary Bit Area
Timer Area
Counter Area
DM Area
EM Area without bank
EM Area with bank
Indirect DM/EM
addresses in binary
Indirect DM/EM
addresses in BCD
Constants
Data Registers
Step program areas
Subroutines
OK
S
CIO 0000 to CIO 6140
W000 to W508
H000 to H508
A000 to A956
T0000 to T4092
C0000 to C4092
D00000 to D32764
E00000 to E32764
En_00000 to En_32764
(n = 0 to C)
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
---
---
Section 3-16
DEGD(850)
@DEGD(850)
Not supported.
Interrupt tasks
OK
D
A448 to A956
673