Nortel DMS-100 Series Maintenance Manual page 673

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

Ground check
At your Current Location
1
Check system grounds.
If grounds
are in good condition
are damaged
2
Use local approved methods to measure ground resistance. The resistance for
each ground must be
If the resistance is
25 Ω
25 Ω
not
3
For additional help, contact the next level of support.
4
The procedure is complete.
DMS-100 Family OPAC Maintenance Manual XPM12 and up
Routine maintenance procedures 13-25
Do
step 2
step 3
25 Ω.
Do
step 4
step 3
Ground check
Ground check
OPAC
OPAC
(continued)
(end)