Nortel DMS-100 Series Maintenance Manual page 363

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

10
To identify the SysB ESA processor, type
>DISP STATE SYSB ESA
and press the Enter key.
If ESA
is SysB
is not SysB
11
To identify the ESA processor with the alarm condition, type
>DISP STATE ISTB ESA
and press the Enter key.
12
To post the ESA processor with the alarm condition, type
>POST ESA esa_no
and press the Enter key.
where
esa_no
is the number of the ESA processor (0 or 1)
Example of a MAP response:
REM1
ESA
13
To busy the posted ESA processor, type
>BSY
and press the Enter key.
Example of MAP response:
This action will take this PM out of service
Please confirm ("Yes" or "No")
>YES
and press the Enter key.
0 SysB
DMS-100 Family OPAC Maintenance Manual XPM12 and up
Alarm clearing procedures 7-127
critical, minor
Do
step 12
step 11
ESA
(continued)