8-140 Card replacement procedures
NT6X60
HIE
(continued)
12
13
At the MSP
14
15
16
At the MAP terminal
17
297-8211-550 Standard 05.01 August 1999
Open the locking levers on the replacement card. Align the card with the slots
in the shelf and gently slide the card into the shelf.
Seat and lock the card.
1. Using your fingers or thumbs, push on the upper and lower edges of the
faceplate to ensure that the card is fully seated in the shelf.
2. Close the locking levers.
Turn ON the circuit breaker turned OFF in step 9.
Remove the wrist strap.
If you were directed to this procedure from the Alarm Clearing Procedures ,
return now to the alarm clearing procedure that directed you here. Otherwise,
continue with step 17.
Return the LCM unit to service by typing
>RTS UNIT unit_no
and pressing the Enter key.
where
unit_no
is the number of the LCM unit (0 or 1)
If RTS
passed
failed
Do
step 18
step 23