Nortel DMS-100 Series Maintenance Manual page 452

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

8-86 Card replacement procedures
NT6X45
HIE
(continued)
Replacing an NT6X45 in an HIE
At your Current Location
1
2
3
At the MAP terminal
4
5
At the HIE
6
7
297-8211-550 Standard 05.01 August 1999
Proceed only if you have been directed to this card replacement procedure from
a step in a maintenance procedure, are using the procedure for verifying or
accepting cards, or have been directed to this procedure by your maintenance
support group.
Obtain a replacement card.
Verify that the replacement card has the same product engineering code (PEC),
including suffix, as the card to be removed.
If you were directed to this procedure from the Alarm Clearing Procedures , go
to step 6.
Otherwise, continue with step 4.
Post the Emergency Stand-Alone (ESA) processor by typing
>MAPCI;MTC;PM;POST ESA esa_no
and pressing the Enter key.
where
esa_no
is the number of the ESA processor
Busy the ESA processor by typing
>BSY
and pressing the Enter key.
Example of a MAP response :
This action will take this PM out of service
Please confirm ("Yes" or "No")
Respond by typing
>YES
and pressing the Enter key.
Replace the NT6X45 card using the procedure replacing a card.
When you have completed the procedure, return here.
If you were directed to this procedure from the Alarm Clearing Procedures ,
return to the alarm clearing procedure that directed you here. Otherwise,
continue with step 8.