7-44 Alarm clearing procedures
RLCM
major
(continued)
At the LCM
6
7
8
At the MAP terminal
9
10
297-8211-550 Standard 05.01 August 1999
Inspect the ringing generator to see if LED is ON.
If the LED
is ON
is OFF
To power up the ringing generator, move the power switch to the ON position.
(The LED turns off.) The switches are identified as:
RG 0
corresponds to LCM unit 0
RG 1
corresponds to LCM unit 1
Determine if power is restored to the ringing generator (RG).
If
turning ON the RG restores power
turning ON the RG does not
restore power
To identify C-side links to the host PM, type:
> TRNSL C
and press the Enter key.
Example of a MAP response:
Link 0: LTC 0
Link 1: LTC 0
To post the host peripheral (LGC, LTC, or RCC), type:
> POST pm pm_no
and press the Enter key.
where
pm
is LGC, LTC, or RCC
pm_no
is the number of the peripheral
Do
step 7
step 16
Do
step 23
step 16
2; Cap MS; Status: OK
6; Cap MS; Status: SysB
;MsgCond: OPN
;MsgCond: OPN