2-32 OPAC maintenance overview

OPAC power requirements

The power requirements for the OPAC at a call rate of 3.0 CCS appear in the
following table.
OPAC power requirements at 3.0 CCS
Drawers
0
1
2
3
4
5
6
7
8
9
10
297-8211-550 Standard 05.01 August 1999
optional equipment current draw (maximum) is 15 A
total frame current is 35.32 A
Lines
0
64
128
192
256
320
384
448
512
576
640
Off–hook
line
demand
Idle frame
current
(A) short:
demand
average
(A)
loops
12
N/A
12.38
0.46 :
0.24
12.67
0.85 :
0.44
13.14
1.23 :
0.64
13.88
1.69 :
0.88
14.26
2.08 :
1.08
14.64
2.46 :
1.28
15.02
2.92 :
1.52
15.40
3.31 :
1.72
15.78
3.70 :
1.92
16.16
4.16 :
2.16
Total
frame
demand
(A) short:
Total
average
frame
loops +
demand
15 A
(A) short:
option
average
load
loops
N/A
N/A
12.84 :
27.84 :
12.62
27.62
13.61 :
28.61 :
13.20
28.20
14.37 :
29.37 :
13.78
25.78
15.57 :
30.57 :
14.76
29.76
16.34 :
31.34 :
15.34
30.34
17.10 :
32.10 :
15.92
30.92
17.94 :
32.94 :
16.54
31.54
18.71 :
33.71 :
17.12
32.12
19.48 :
34.48 :
17.70
32.70
20.32 :
35.32 :
18.32
33.32