Nortel DMS-100 Series Maintenance Manual page 395

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

At the RMM
5
WARNING
Static electricity damage
Wear a wrist strap connected to the wrist strap
grounding point at the top of each equipment rack,
(Bay 0, 1, 2, and 3), while handling circuit cards. This
protects the cards against damage caused by static
electricity.
Replace the NT2X11 card using the procedure "Replacing a card." When you
have completed the procedure, return here.
At the MAP terminal
6
Post the RMM trunk circuits by typing
>POST P RMM rmm_no ckt_no to ckt_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf where the card is to be replaced
ckt_no
is the number of the trunk circuit associated with the card to be
replaced
7
Go to the PM level of the MAP screen, place the first circuit in a hold position
and test the second circuit by typing
>HOLD
and pressing the Enter key
and then typing
>TST
and pressing the Enter key.
If TST
passed
failed
DMS-100 Family OPAC Maintenance Manual XPM12 and up
Card replacement procedures 8-29
RMM
Do
step 8
step 14
NT2X11
(continued)