Nortel DMS-100 Series Maintenance Manual page 652

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

13-4 Routine maintenance procedures
Battery capacity test
OPAC
(continued)
Battery capacity test
At the MAP terminal
1
2
3
4
297-8211-550 Standard 05.01 August 1999
Make sure extended power failures did not occur at the OPAC site in the last 72
hours. Make sure that the OPAC is not in post-ac failure recovery mode.
To access the OPMPES MAP display level, type
>MAPCI;MTC;PM;PES
and press the Enter key.
To post the correct alarm state, type
>POST alarm_state
and press the Enter key.
where
alarm_state
is RED, AMBER, GREEN, or OFFL
Note: This command posts all the peripheral modules (PM) in the named
alarm state, and displays the first PM in the set. Use the NEXT command to
scroll through the posted PMs until the correct OPAC appears in the MAP
terminal.
To disable the automatic battery rotation and testing, type
>AUDIT DISABLE
and press the Enter key.