Nortel DMS-100 Series Maintenance Manual page 448

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

8-82 Card replacement procedures
NT6X21
LCM
(continued)
6
At the LCM
7
At the MAP terminal
8
9
10
11
12
297-8211-550 Standard 05.01 August 1999
Busy the line by typing
>BSY
and pressing the Enter key.
Go to the procedure for Replacing a line card. When you have completed the
procedure, return to this point.
Test the line card just replaced by typing
>DIAG
and pressing the Enter key.
If the DIAG
passed
failed
Return the line card to service by typing
>RTS
and pressing the Enter key.
If RTS
passed
failed
Send any faulty cards for repair according to local procedure.
Record the following items in office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card
Go to step 13.
Obtain further assistance in replacing this card by contacting the personnel
responsible for higher level of support.
Do
step 9
step 12
Do
step 10
step 12

Advertisement

Table of Contents
loading

Table of Contents