Nortel DMS-100 Series Maintenance Manual page 551

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

31
Return the ESA to service by typing
>RTS
and pressing the Enter key.
If the RTS
passes
fails
32
Send any damaged cards for repair according to local procedure.
33
Record the following items in office records:
date the card was replaced
serial number of the card
problems that required replacement of the card
Go to step 36.
34
Return to the Alarm Clearning Procedure that referred you to this procedure. If
necessary, go to the point where the damaged card list was produced, identify
the next damaged card on the list, and go to the appropriate procedure for that
card in this manual.
35
Contact the next level of support for additional help to replace this card.
36
You have completed this procedure. Return to the maintenance procedure that
referred you to this card replacement procedure and continue.
DMS-100 Family OPAC Maintenance Manual XPM12 and up
Card replacement procedures 8-185
HIE
Do
step 32
step 35
NTMX45
NTMX45
HIE
(continued)
(end)