Nortel DMS-100 Series Maintenance Manual page 260

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

7-24 Alarm clearing procedures
LCM (RG)
LCM (RG)
critical
critical
(continued)
(end)
16
17
18
19
297-8211-550 Standard 05.01 August 1999
To align RG activity to the preferred RG, type
>SWRG UNIT unit_no
and press the Enter key.
where
unit_no
is the LCM unit (0 or 1) associated with the new RG
Example of a MAP display:
LCM REM1 00 0 InSv Links
Unit 0: InSv
/RG:0
Unit 1: InSv
/RG:0
Drwr:
01
23
45
67
..
..
..
..
Note: Repeat this step until both units of the LCM are on the preferred RG.
If the SWRG command
passes
fails
Go to Card Replacement Procedures . Replace the first card on the list. When
you complete the card replacement procedures, go to step 11 of this procedure.
For additional help to clear this alarm, contact the next level of support.
This procedure is complete.
If other alarms appear, refer to the appropriate procedures to clear the indicated
alarms.
OOS: Cside 0 Pside 0
11
11
11
11
11
89
01
23
45
67
89
..
..
..
..
..
..
Do
step 18
step 19
RG: Pref 0 InSv
Stby 1 InSv