Download From The Pc Using Startdrive - Siemens SINAMICS G110M Operating Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

7. To start commissioning of the safety functions, set p10 = 95.
8. Enter the password for the safety functions in p9761.
9. To confirm the settings of the safety functions, set p9701 = AC.
10.To exit commissioning of the safety functions, set p10 = 0.
11.Back up the settings so that they are protected against power failure.
12.Switch off the converter power supply.
13.Wait until all LEDs on the converter are dark.
14.Switch on the converter power supply again.
15.Perform a reduced acceptance test.
(Page 387)
You have replaced the converter and transferred the safety function settings from the operator
panel to the new converter.
10.2.2.3

Download from the PC using Startdrive

Overview
You can transfer the converter settings that have been backed up to a PC back to the converter.
Requirement
The following preconditions apply:
• The converter power supply has been switched on.
• The PC and converter are connected with one another via a USB cable or via the fieldbus.
• The converter settings are not protected against copying.
Function description
Procedure
1. In Startdrive, open the project that matches the drive.
2. Select "Load to device".
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Reduced acceptance test after component replacement and firmware change
Download with active know-how protection with copy protection (Page 375)
Corrective maintenance
10.2 Downloading the converter settings
373