Advertisement

5. Evaluate your drive response.
– If the motor decelerates too slowly, then reduce the ramp-down time.
– Extend the ramp-down time if the motor is braked too quickly or the converter goes into
6. Repeat steps 1 ... 5 until the drive behavior meets the requirements of the machine or plant.
You have set the extended ramp-function generator.
Basic ramp-function generator
When compared to the extended ramp-function generator, the basic ramp-function generator
has no rounding times.
Parameter
Table 8-59
Parame‐
ter
p1082[D] Maximum speed
p1115
p1120[D] Ramp-function generator ramp-up time
p1121[D] Ramp-function generator ramp-down time
p1135[D] OFF3 ramp-down time
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
The minimum ramp-down time that makes sense depends on your particular application.
Depending on the Power Module used, for an excessively short ramp-down time, the
converter either reaches the motor current, or the DC link voltage in the converter
becomes too high.
a fault condition when braking.
Parameters for setting the ramp-function generator
Description
Ramp-function generator selection
Advanced commissioning
8.17 Setpoint calculation
Factory setting
1500 rpm
1
10 s
10 s
30 s