Defining the function of an analog input
You define the analog input function by connecting a connector input of your choice with
parameter p0755. Parameter p0755 is assigned to the corresponding analog input via its index,
i.e. parameter p0755[0] is assigned to analog input 0.
Parameters
Table 8-7
Parameter
p1070[C]
p1075[C]
p1503[C]
p1511[C]
p1522[C]
p2253[C]
p2264[C]
A complete list of connector inputs is provided in the parameter list.
Further information
Signal smoothing
When required, you can smooth the signal, which you read-in via an analog input, using
parameter p0753.
Additional information is provided in the parameter list and in function diagram 2251.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Additional settings for parameter p0756
Unipolar voltage input
Unipolar voltage input with monitoring
Unipolar current input
Unipolar current input with monitoring
Unipolar voltage input
Connector inputs (CI) of the converter (selection)
Description
CI: Main setpoint
CI: Supplementary setpoint
CI: Torque setpoint
CI: Supplementary torque 1
CI: Torque limit, upper
CI: Technology controller setpoint 1
CI: Technology controller actual value
Manuals and technical support (Page 415)
8.4 Adapt the default setting of the inputs and outputs
0 V ... +10 V
+2 V ... +10 V
0 mA ... +20 mA
+4 mA ... +20 mA
0 V ... +3 V
Advanced commissioning
Factory setting
0
0
0
0
1520
0
0
167