Installation
4.3 Electrical Installation
PROFIBUS terminal diagram
X03
X04
PROFINET terminal diagram
X03
X04
AS-i terminal diagram
X03
24V Power supply - USS, PROFIBUS, PROFINET
The unswitched 24 V power supply (1L+) is required for the device to function.
• Use a power supply with PELV (Protective Extra Low Voltage).
• For applications in USA and Canada: Use a power supply NEC Class 2.
• The 0 V of the power supply must be connected with low resistance to the PE of the system.
The switched 24 V (2L+) supplies the two digital outputs. Switching off brings all of the actuators
connected to the digital outputs into the no-voltage state.
72
1
4
5
2
3
2
1
5
3
4
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
M12 connector, 5 Pole, male
M12 connector, 5 Pole, female
M12 connector, 4 Pole, female
M12 connector, 4 Pole, female
M12 connector, 5 Pole, female