Advanced commissioning
8.27 Monitoring the driven load
When using the control mode "U/f control" (p1300 < 10), the "Blocking protection" function
becomes active when the current limit is reached.
Setting pump monitoring
1. Set p2193 = 4.
2. The converter sets the monitoring as shown.
Figure 8-75
Default settings for pumps
3. The converter sets monitoring response p2181 = 7
4. If necessary, adjust the speed thresholds p2182 ... p2184.
5. If necessary, adjust the torque threshold for each speed.
The converter displays the current torque in r0031.
You have now set monitoring.
334
No-load monitoring (Page 330)
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL