Precondition
The following requirements apply:
• The converter power supply has been switched on.
• The converter settings are not protected against copying.
Function description
Procedure
1. Connect the operator panel to the converter.
2. Start the download.
3. Wait until the download is completed.
4. After loading, check whether the converter outputs Alarm A01028.
– Alarm A01028:
– No alarm A01028: Proceed with the next step.
5. Back up the settings so that they are protected against power failure.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Download with active know-how protection with copy protection (Page 375)
The loaded settings are not compatible with the converter.
Delete the alarm with p0971 = 1.
Recommission the drive.
Corrective maintenance
10.2 Downloading the converter settings
369