Siemens SINAMICS G110M Operating Instructions Manual page 131

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

1. Open the control panel.
2. Assume master control for the converter.
3. Set the "Drive enables"
4. Switch on the motor.
The converter starts the motor data identification. This measurement can take several
minutes.
Depending on the setting, after motor data identification has been completed, the converter
switches off the motor - or it accelerates it to the currently set setpoint.
5. If required, switch off the motor.
6. Relinquish the master control after the motor data identification.
7. Save the settings in the converter (RAM → EEPROM):
You have completed the motor data identification.
Self-optimization of the speed control
If you have not only selected motor data identification with the motor stationary, but also
rotating measurement with self-optimization of the speed control, you must switch on the
motor again as described above and wait for the optimization run to finish.
Quick commissioning has been completed once the motor data identification has been
successfully completed.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Commissioning
5.4 Quick commissioning
129