Setting fan and compressor monitoring
1. Set p2193 = 5.
2. The converter sets the monitoring as shown.
Figure 8-76
Default settings for fans and compressors
3. The converter sets monitoring response p2181 = 7
4. If necessary, adjust the speed thresholds p2182 ... p2184.
5. Set the torque threshold for each speed.
The converter displays the current torque in r0031.
You have now set monitoring.
❒
Parameter
Number
r0031
p0311[M]
r0333[M]
p1080[D]
p1082[D]
p1300[D]
p2165[D]
p2168[D]
p2181[D]
p2182[D]
p2183[D]
p2184[D]
p2186[D]
p2188[D]
p2190[D]
p2191[D]
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Name
Torque actual value, smoothed
Rated motor speed
Rated motor torque
Minimum speed
Maximum speed
Open-loop/closed-loop control operating mode
Load monitoring blocking monitoring threshold, upper
Load monitoring blocking monitoring torque threshold
Load monitoring, response
Load monitoring, speed threshold 1
Load monitoring, speed threshold 2
Load monitoring, speed threshold 3
Load monitoring torque threshold 1, lower
Load monitoring torque threshold 2, lower
Load monitoring torque threshold 3, lower
Load monitoring torque threshold, no load
Advanced commissioning
8.27 Monitoring the driven load
Factory setting
-
0 rpm
-
0 rpm
1500 rpm
See parameter list
0 rpm
10000000 Nm
0
150 rpm
900 rpm
1500 rpm
0 Nm
0 Nm
0 Nm
0 Nm
335