8.6.5

NAMUR message word

Function description
Fault word according to the VIK-NAMUR definition (MELD_NAMUR)
Bit Significance
0
1
2
3
4
5
6
7
8
10 1 = fault in the internal converter communication
11 1 = line fault
15 1 = other fault
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
1 = Control Unit signals a fault
1 = line fault: Phase failure or inadmissible voltage
1 = DC link overvoltage
1 = Power Module fault, e.g. overcurrent or overtemperature
1 = converter overtemperature
1 = ground fault/phase fault in the motor cable or in the motor
1 = motor overload
1 = communication error to the higher-level control system
1 = fault in a safety-relevant monitoring channel