Advanced commissioning
8.17 Setpoint calculation
Parameter
Table 8-58
Parameter
p1115
p1120[D]
p1121[D]
p1130[D]
p1131[D]
p1134[D]
p1135[D]
p1136[D]
p1137[D]
Additional information is provided in the parameter list of the List Manual.
Setting the extended ramp-function generator
Procedure
1. Enter the highest possible speed setpoint.
2. Switch on the motor.
3. Evaluate your drive response.
– If the motor accelerates too slowly, then reduce the ramp-up time.
– If the motor accelerates too fast, then extend the ramp-up time.
– Increase the initial rounding if the acceleration is jerky.
– In most applications, it is sufficient when the final rounding is set to the same value as the
4. Switch off the motor.
276
Additional parameters to set the extended ramp-function generator
Description
Ramp-function generator selection
Ramp-function generator ramp-up time
Ramp-function generator ramp-down time
Ramp-function generator initial rounding time
Ramp-function generator final rounding time
Ramp-function generator round‐
ing type
0: Continuous smoothing
1: Discontinuous smoothing
OFF3 ramp-down time
OFF3 initial rounding time
OFF3 final rounding time
An excessively short ramp-up time means that the motor will reach its current limiting
when accelerating, and will temporarily not be able to follow the speed setpoint. In this
case, the drive exceeds the set time.
initial rounding.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Factory setting
1
10 s
30 s
0 s
2 s
0
30 s / 0 s
2 s / 0 s
0 s