Checking the assignment of the digital inputs

Overview
The simultaneous connection of digital inputs with a safety function and a "standard" function
may lead to the drive behaving in unexpected ways.
If you control the safety functions in the converter via failsafe digital inputs, then you must check
as to whether the failsafe digital inputs are in some instances interconnected with a "standard"
function.
Function description
Procedure
1. Select the screen for the digital inputs.
2. Remove all interconnections of the digital inputs that you use as failsafe digital input F-DI:
3. You must delete the digital input connections for all CDS if you use the switchover of the
command data sets (CDS).
You can find a description of the CDS switchover in the operating instructions.
You have ensured that the failsafe digital inputs only control the safety functions in the
converter.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Description
Drive commissioning parameter filter
Save parameters
SI copy function
Acknowledge SI data change
Advanced commissioning
8.15 Safe Torque Off (STO) safety function
Factory setting
1
0
0000 hex
0000 hex
255