Siemens SINAMICS G110M Operating Instructions Manual page 189

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Bit Significance
11 Reserved
12 1 = torque control active
13 1 = no external fault
14 Not used
15 1 = CDS bit 1
If you switch from telegram 350 to a different one, then the converter sets all interconnections p1020,
1)
... to "0". Exception: p2106 = 1.
Status word 3 (ZSW3)
Bit Significance
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Telegram 350
0 = speed control active
0 = external fault is active (F07860)
1 = DC braking active
1 = |n_act | > p1226
1 = |n_act | > p1080
1 = i_act ≧ p2170
1 = |n_act | > p2155
1 = |n_act | ≦ p2155
1 = |n_act | ≧ r1119
1 = DC link voltage ≦ p2172
1 = DC link voltage > p2172
1 = ramp-up or ramp-down completed Ramp-function generator is not ac‐
1 = technology controller output at
the lower limit
1 = technology controller output at
the upper limit
Not used
Not used
Not used
Not used
8.6 Drive control via PROFIBUS or PROFINET
Explanation
Changes over the control mode
for vector control.
--
Changes over between settings
for different operation interfaces
(command data sets).
Description
--
Absolute current speed > stationary
state detection
Absolute actual speed > minimum
speed
Actual current ≥ current threshold
value
Absolute actual speed > speed
threshold value 2
Absolute actual speed < speed
threshold value 2
Speed setpoint reached
Actual DC link voltage ≦ threshold
value
Actual DC link voltage > threshold
value
tive.
Technology controller output ≦
p2292
Technology controller out‐
put > p2291
Advanced commissioning
Signal interconnec‐
tion in the converter
p1501[0] = r2093.12
p2106[0] = r2093.13
p0811[0] = r2093.15
Signal intercon‐
nection in the
converter
p2051[3] = r0053
187
1)