Corrective maintenance
10.2 Downloading the converter settings
3. Connect Startdrive online with the drive.
The converter signals faults after the download. Ignore these faults, as they will be
automatically acknowledged by the following steps.
4. Press the "Start safety commissioning" button.
5. Enter the password for the safety functions.
6. Press the "End safety commissioning" button.
7. Confirm the prompt for saving your settings (copy RAM to ROM).
8. Disconnect the online connection.
9. Switch off the converter power supply.
10.Wait until all LEDs on the converter are dark.
11.Switch on the converter power supply again.
12.Perform a reduced acceptance test.
(Page 387)
You transferred the settings from the PC to the new converter.
374
Reduced acceptance test after component replacement and firmware change
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL