Table 8-2
Commands for switching the motor on and off
ON
The inverter switches the motor on.
Jogging 1
Jogging 2
Enable operation
OFF1, OFF3
The inverter brakes the motor. The inverter switches off the motor once it comes to a standstill.
The motor is considered to be stationary if the speed is less than a defined minimum speed.
OFF2
The inverter switches off the motor immediately without first braking it.
Inhibit operation
Parameter
Parameter
Description
p1226
Standstill detection, speed
threshold [rpm]
p1227
Standstill detection monitor‐
ing time [s]
p1228
Pulse cancellation delay time
[s]
Further information
You will find additional information in function diagram 2610 of the List Manual.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
8.3 Sequence control when switching the motor on and off
Setting
Factory setting: 20.00
rpm
Factory setting: 300.00 s
Factory setting: 0.01 s
Advanced commissioning
The inverter identifies that the motor is at a
standstill after OFF1 or OFF3 when at least one
of the following conditions has been satisfied:
The speed actual value falls below the thresh‐
old in p1226 and the time started in p1228
has expired.
The speed setpoint falls below the threshold
in p1226, and the time subsequently started
in p1227 has expired.