Pt1000 sensor
Using a Pt1000 sensor, the converter monitors the motor temperature and the sensor itself for
wire breakage and/or short-circuit:
• Temperature monitoring:
Using a Pt1000 sensor, the converter evaluates the motor temperature in the range from
-48 °C ... +248 °C.
Set the temperature for the alarm and fault thresholds with parameter p0604 or p0605.
– Overtemperature alarm (A07910):
– Overtemperature fault (F07011):
• Sensor monitoring (A07015 or F07016):
– Wire-break:
– Short-circuit:
Parameter
Parameter
p0335[[M]
p0601[0...n]
p0604[0...n]
p0605[M]
p0610[M]
p0640[D]
Additional information on the motor temperature monitoring can be found in function
diagram 8016 of the List Manual.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
- motor temperature > p0604 and p0610 = 0
The converter responds with a fault in the following cases:
- motor temperature > p0605
- motor temperature > p0604 and p0610 > 0
The converter interprets a resistance > 2120 Ω as a wire-break and outputs the alarm
A07015. After 100 milliseconds, the converter changes to the fault state with F07016.
The converter interprets a resistance < 603 Ω as a short-circuit and outputs the alarm
A07015. After 100 milliseconds, the converter changes to the fault state with F07016.
Description
Type of motor cooling
Motor temperature sensor type
Mot_temp_mod 2/sensor alarm threshold
Mot_temp_mod 1/2/sensor threshold and temperature value 145 °C
Motor overtemperature response
Current limit
Advanced commissioning
8.23 Motor protection with temperature sensor
Factory setting
0
0
130 °C
12
0 Arms
325