11.7 Protecting persons from electromagnetic fields

11.7
Protecting persons from electromagnetic fields
Overview
Protection of workers from electromagnetic fields is specified in the European EMF Directive
2013/35/EU. This directive is implemented in national law in the European Economic Area (EEA).
Employers are obligated to design workplaces in such a way that workers are protected from
impermissibly strong electromagnetic fields.
To this end, assessments and/or measurements must be performed for workplaces.
Requirement
1. The laws for protection from electromagnetic fields in force in individual EU member states
can go beyond the minimum requirements of the EMF Directive 2013/35/EU and always take
precedence.
2. The ICNIRP 2010 limits for the workplace are the basis for the assessment.
3. The 26th BImSchV (German Federal Emission Protection Regulation) defines 100 μT (RMS)
for the assessment of active implants.
According to Directive 2013/35/EU, 500 µT (RMS) at 50 Hz is applicable here.
4. Compliance with the limit values was assessed for the following frequencies:
– Line frequency 47 ... 63 Hz
– Pulse frequency, for example 4/8/16 kHz and multiples thereof, assessed up to a
5. The routing of power cables has a significant impact on the electromagnetic fields that occur.
Install and operate the components in compliance with what is specified in the
documentation and use shielded motor cables.
Description
The following information regarding electromagnetic fields relates solely to converters supplied
by Siemens.
The converters are normally used in machines. The assessment and testing is based on
DIN EN 12198.
The indicated minimum distances apply to the head and complete torso of the human body.
Shorter distances are possible for extremities.
Table 11-6
396
maximum of 100 kHz
EMC installation guidelines (Page 62)
Minimum distances to the converter
Individuals without active implants
Forearm length (approx. 35 cm)
Individuals with active implants
Must be separately assessed depending on the ac‐
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
tive implant.