List Of Alarms And Faults - Siemens SINAMICS G110M Operating Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

9.7

List of alarms and faults

Axxxxx Alarm
Fyyyyy: Fault
Table 9-11
The most important alarms and faults
Number
Cause
F01000
Software fault in CU
F01001
Floating Point Exception
F01015
Software fault in CU
F01018
Power-up aborted more than once
A01028
Configuration error
F01033
Unit switchover: Reference parame‐
ter value invalid
F01034
Unit switchover: Calculation of the
parameter values after reference
value change unsuccessful
F01040
Parameters must be saved
F01044
Loading of memory data card defec‐
tive
F01105
CU: Insufficient memory
A01101
Memory card not available
F01122
Frequency at the probe input too
high
F01205
CU: Time slice overflow
F01250
CU hardware fault
F01512
An attempt has been made to estab‐
lish an conversion factor for scaling
which is not present
A01590
Motor maintenance interval lapsed
F01662
CU hardware fault
A01900
PROFIBUS: Configuration telegram
faulty
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Remedy
Replace CU.
Switch CU off and on again.
Upgrade firmware or contact technical support.
1. Switch the module off and on again.
2. After this fault has been output, the module is booted with the factory
settings.
3. Recommission the converter.
Explanation: Parameterization on the memory card has been created with a
different type of module (article number, MLFB)
Check the module parameters and recommission if necessary.
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
Select the value of the reference parameter so that the parameters involved
can be calculated in the per unit notation (p0304, p0305, p0310, p0596,
p2000, p2001, p2002, p2003, r2004).
Save parameters (p0971).
Switch CU off and on again.
Replace memory card or CU.
Reduce number of data records.
Insert a memory card or disable the warning A01101.
Message for a memory card that is not inserted (Page 140)
Reduce the frequency of the pulses at the probe input.
Contact technical support.
Replace CU.
Create scaling or check transfer value.
Carry out maintenance and reset the maintenance interval (p0651).
Switch CU off and on again, upgrade firmware, or contact technical support.
Explanation: A PROFIBUS master is attempting to establish a connection
with a faulty configuration telegram.
Check the bus configuration on the master and slave side.
Alarms, faults and system messages
9.7 List of alarms and faults
357