Advanced commissioning

8.7 Control via AS-i

8.7
Control via AS-i
8.7.1

Single slave mode

In Single Slave mode, four bits are available for the communication between the AS-i master and
the converter. The four bits are used to transfer process data. In parallel, the control can start a
diagnostic request via AS-i.P0.
The following default settings are available; both work with profile 7.F.E.
• Default setting 30: Standard Single Slave mode
• Default setting 32: Modified Single Slave mode
Default setting 30: Standard Single Slave mode
In standard addressing, the control specifies the speed setpoint via the motor control bits (AS-
i.DO0 ... AS-i.DO3).
Control -> converter
• AS-i.DO0
• AS-i.DO1
• AS-i.DO2
• AS-i.DO3
1171856).
Converter -> control
If the control specifies the speed setpoint, the converter replies:
• p2080[0] = 53.13 ->
• p2080[1] = 899.11 ->
• p2080[2] = 722.0 ->
• p2080[3] = 722.1 ->
If the control sends a diagnostic request via AS-i.P0, the converter replies with the currently
pending fault or alarm messages.
1171856).
Default setting 32: Modified Single Slave mode
In Single Slave mode with modified addressing the control specifies the following:
208
->
p1020 = 2093.0
->
p1021 = 2093.1
->
p1022 = 2093.2
->
p1023 = 2093.3
AS-i System Interface Manual
AS-i.DI0
AS-i.DI1
AS-i.DI2
AS-i.DI3
AS-i System Interface Manual
Fixed speed bit 0
Fixed speed bit 1
Fixed speed bit 2
Fixed speed bit 3
(https://support.industry.siemens.com/cs/gb/en/view/
Operational enable for PLC
Pulses enabled
State DI0
State DI1
(https://support.industry.siemens.com/cs/gb/en/view/
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL