Alarms, faults and system messages
9.7 List of alarms and faults
Number
Cause
F07902
Motor stalled
A07903
Motor speed deviation
A07910
Motor overtemperature
A07920
Torque/speed too low
A07921
Torque/speed too high
A07922
Torque/speed out of tolerance
F07923
Torque/speed too low
F07924
Torque/speed too high
A07927
DC braking active
A07980
Rotary measurement activated
A07981
No enabling for rotary measurement Acknowledge pending faults.
A07991
Motor data identification activated
F08501
Setpoint timeout
F08502
Monitoring time sign-of-life expired •
F08510
Send configuration data not valid
A08511
Receive configuration data not valid
A08526
No cyclic connection
A08565
Consistency error affecting adjusta‐
ble parameters
F13100
Know-how protection: Copy protec‐
tion error
F13101
Know-how protection: Copy protec‐
tion cannot be activated
360
Remedy
Check whether the motor data has been parameterized correctly and per‐
form motor identification.
Check the current limits (p0640, r0067, r0289). If the current limits are too
low, the drive cannot be magnetized.
Check whether motor cables are disconnected during operation.
Increase p2163 and/or p2166.
Increase the torque, current and power limits.
Check the motor load.
Check the motor's ambient temperature.
Check the KTY84 or Pt1000 sensor.
Check the overtemperatures of the thermal model (p0626 ... p0628).
The torque deviates from the torque/speed envelope curve.
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
Not required
Not required
Establish missing enables (see r00002, r0046).
Switch on the motor and identify the motor data.
Check the PROFINET connection.
Set the controller to RUN mode.
If the error occurs repeatedly, check the set monitoring time p2044.
Check the PROFINET connection.
Check the PROFINET configuration
Activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
The know-how protection and the copy protection for the memory card are
active. An error occurred during checking of the memory card.
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
Insert a valid memory card.