Siemens SINAMICS G110M Operating Instructions Manual page 360

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Alarms, faults and system messages
9.7 List of alarms and faults
Number
Cause
A01910
Setpoint timeout
F01910
A01920
PROFIBUS: Cyclic connection inter‐
rupt
F03505
Analog input, wire break
A03520
Temperature sensor fault
A05000
Power Module overtemperature
A05001
A05002
A05004
A05006
F06310
Supply voltage (p0210) incorrectly
parameterized
F07011
Motor overtemperature
A07012
I2t Motor Module overtemperature
A07015
Motor temperature sensor alarm
F07016
Motor temperature sensor fault
F07086
Unit switchover: Parameter limit vi‐
F07088
olation
F07320
Automatic restart aborted
A07321
Automatic restart active
F07330
Search current measured too low
358
Remedy
The alarm is generated when p2040 ≠ 0 ms and one of the following causes
is present:
The bus connection is interrupted
The MODBUS master is switched off
Communications error (CRC, parity bit, logical error)
An excessively low value for the fieldbus monitoring time (p2040)
Explanation: The cyclic connection to PROFIBUS master is interrupted.
Establish the PROFIBUS connection and activate the PROFIBUS master with
cyclic operation.
Check the connection to the signal source for interrupts.
Check the level of the signal supplied.
The input current measured by the analog input can be read out in r0752.
Check that the sensor is connected correctly.
Check the following:
- Is the ambient temperature within the defined limit values?
- Are the load conditions and duty cycle configured accordingly?
- Has the cooling failed?
Check the parameterized supply voltage and if required change (p0210).
Check the line voltage.
Reduce the motor load.
Check ambient temperature.
Check the wiring and connection of the sensor.
Check and if necessary reduce the motor load.
Check the motor's ambient temperature.
Check thermal time constant p0611.
Check overtemperature fault threshold p0605.
Check that the sensor is connected correctly.
Check the parameter assignment (p0601).
Make sure that the sensor is connected correctly.
Check the parameterization (p0601).
Deactivate the temperature sensor fault (p0607 = 0).
Check the adapted parameter values and if required correct.
Increase the number of restart attempts (p1211). The actual number of start
attempts is shown in r1214.
Increase the wait time in p1212 and/or monitoring time in p1213.
Connect an ON command (p0840).
Increase the monitoring time of the power unit or switch off (p0857).
Reduce the wait time for resetting the fault counter p1213[1] so that fewer
faults are registered in the time interval.
Explanation: The automatic restart (AR) is active. During voltage recovery
and/or when remedying the causes of pending faults, the drive is automat‐
ically switched back on.
Increase search current (p1202), check motor connection.
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Distributed converter for SIMOGEAR geared motors

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents