3. Perform a "Copy from RAM to ROM".
4. Set parameter p0726 to 1.
5. When the motor data save is complete, parameter p0726 will be set back to 0.
6. The motor data is saved to the converter's EEPROM.
You saved your unique motor data to the converter's EEPROM.
Note
Saving motor data to the EEPROM is permanent
When the motor data is saved the converter's EEPROM, the data is permanently stored in the
EEPROM and will never be overwritten by any reset function of the converter.
To change the motor data stored in the EEPROM, the procedure outlined above must be
performed again with the new required motor data.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Commissioning
5.5 Restoring the factory settings
131