MX240 3D Universal Edge Router Hardware Guide

MX240 Router Grounding Cable Lug Specifications

MX240 Router Grounding Cable Specifications

158

Figure 44: Connecting DC Power to the Router

The accessory box shipped with the router includes one cable lug that attaches to the
grounding cable (see
Figure 45 on page
the grounding cable to the grounding points.

Figure 45: Grounding Cable Lug

End view
0.28
diameter
0.55
each hole
0.08
0.25
0.625
CAUTION:
Before router installation begins, a licensed electrician must attach
a cable lug to the grounding and power cables that you supply. A cable with
an incorrectly attached lug can damage the router.
NOTE:
The same cable lug is used for the DC power cables.
You must provide one grounding cable that meets the following specifications: 6-AWG
2
(13.3 mm
), minimum 60°C wire, or as required by the local code.
158) and two UNC 1/4–20 screws used to secure