TROUBLESHOOTING
General
The following LEDs of the CLIF-CBUSLC can be used for troubleshooting purposes:
Power LED (green)
Status LED (red)
L2 LED (yellow)
Tx (sending data on RS485-1) and Rx (receiving data on RS485-1) LED
Power LED (green) of CLIF-CBUSLC
case power LED
meaning
ON
Normal operation
1
Power supply not OK.
OFF
2
Status LED (red) of CLIF-CBUSLC
case status LED
meaning
Normal operation.
1
OFF after
power-up
2
ON con-
– No or invalid firmware
tinuously after
power-up
L2 LED
case bus LEDs
meaning
A SUSI client (ARENA
1
ON
ARENA 3.0) is connected
continuously
after power-up
No client is connected
2
Dark
Tx and Rx LEDs
case bus LEDs
meaning
Normal operation; RS485-1 is functioning
1
Both Tx and Rx
properly.
are flashing
No communication on RS485-1.
2
Both Tx and Rx
are OFF
Communication on RS485-1 has been
3
Rx is flashing
switched OFF, but the CLIF-CBUSLC is
and Tx is OFF
receiving data from controllers.
The CLIF-CBUSLC is attempting to establish
4
Tx is flashing
communication on RS485-1, but there is no
and Rx is OFF
answer.
CLIF-CBUSLC INTERFACE – INSTALLATION & COMMISSIONING INSTRUCTIONS
Table 16. CLIF-CBUSLC power LED
Table 17. CLIF-CBUSLC status LED
Table 18. CLIF-CBUSLC L2 LED
AX
AX
, COACH
Table 19. CLIF-CBUSLC Tx and Rx LEDs
remedy
No action necessary.
Check power supply voltage.
►
Check wiring.
►
If problem persists, replace hardware.
►
remedy
No action necessary.
Try powering down and then powering up the CLIF-
►
CBUSLC.
If problem persists, replace hardware.
►
remedy
or
No action necessary.
If you are unable to establish communication, check
►
IP address, SUSI port number, ...
remedy
No action necessary
Switch ON communication on RS485-1. Further
►
handling like case 4 (below).
Use client to establish a connection with correct
►
device ID and baud rate
The communication rate (Kbaud) on RS485-1 has
►
not been correctly set; controllers on the C-Bus may
have been setup incorrectly; wiring problem or
hardware defect.