TROUBLESHOOTING

General

The following LEDs of the CLIF-CBUSLC can be used for troubleshooting purposes:
Power LED (green)
Status LED (red)
L2 LED (yellow)
Tx (sending data on RS485-1) and Rx (receiving data on RS485-1) LED

Power LED (green) of CLIF-CBUSLC

case power LED
meaning
ON
Normal operation
1
Power supply not OK.
OFF
2

Status LED (red) of CLIF-CBUSLC

case status LED
meaning
Normal operation.
1
OFF after
power-up
2
ON con-
– No or invalid firmware
tinuously after
power-up

L2 LED

case bus LEDs
meaning
A SUSI client (ARENA
1
ON
ARENA 3.0) is connected
continuously
after power-up
No client is connected
2
Dark

Tx and Rx LEDs

case bus LEDs
meaning
Normal operation; RS485-1 is functioning
1
Both Tx and Rx
properly.
are flashing
No communication on RS485-1.
2
Both Tx and Rx
are OFF
Communication on RS485-1 has been
3
Rx is flashing
switched OFF, but the CLIF-CBUSLC is
and Tx is OFF
receiving data from controllers.
The CLIF-CBUSLC is attempting to establish
4
Tx is flashing
communication on RS485-1, but there is no
and Rx is OFF
answer.
CLIF-CBUSLC INTERFACE – INSTALLATION & COMMISSIONING INSTRUCTIONS
Table 16. CLIF-CBUSLC power LED
Table 17. CLIF-CBUSLC status LED
Table 18. CLIF-CBUSLC L2 LED
AX
AX
, COACH
Table 19. CLIF-CBUSLC Tx and Rx LEDs
remedy
No action necessary.
Check power supply voltage.
Check wiring.
If problem persists, replace hardware.
remedy
No action necessary.
Try powering down and then powering up the CLIF-
CBUSLC.
If problem persists, replace hardware.
remedy
or
No action necessary.
If you are unable to establish communication, check
IP address, SUSI port number, ...
remedy
No action necessary
Switch ON communication on RS485-1. Further
handling like case 4 (below).
Use client to establish a connection with correct
device ID and baud rate
The communication rate (Kbaud) on RS485-1 has
not been correctly set; controllers on the C-Bus may
have been setup incorrectly; wiring problem or
hardware defect.
21
EN1Z-1026GE51 R0417