Jog Run Mode - Toshiba Tosvert VF-S15 Instruction Manual

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

Output frequency [Hz]
ll+f391
ll
Forward/ reverse
Note: This function is valid when doing forward/reverse switching.

6.14 Jog run mode

6
f260 : Jog run frequency
f261 : Jog run stopping pattern
f262 : Panel jog run mode
 Function
Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal immediately
generates a jog run frequency output irrespective of the designated acceleration time.
Also, you can choose the jog run start/stop mode from the panel.
Assign 18: jog run mode to an input terminal.
Ex) When assigning it to the RES terminal: f113 to 18.
The motor can be operated in jog mode while the assigned input terminals are connected (RES-CC ON).
[Parameter setting]
Title
f260
f261
f262


When starting operation, f256 function will not work until output frequency reaches ll.
When the output frequency exceeds ll, f259 function will be invalid until operation signal is OFF.
Function
Jog run frequency
Jog run stopping
pattern
Panel jug run mode


Adjustment range
f240-20.0 (Hz)
0: Deceleration stop
1: Coast stop
2: DC braking
0: Invalid
1: Valid
F-50
E6582175
Time[s]
ON
OFF
Default setting
5.0
0
0