Jog Run Mode - Toshiba TOSVERT VF-MB1 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

6.10 Jog run mode

f260 : Jog run frequency
f261 : Jog run stopping pattern
f262 : Panel jog run mode
 Function
Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal generates a jog
run frequency output at once, irrespective of the designated acceleration time.
Also, you can choose an operation panel start/stop mode between the ordinary start/stop mode and the
jog run start/stop mode.
The jog run function needs to be assigned to an input terminal. When assigning it to the RES terminal, set
f113 to 18 .
The motor can be operated in jog mode while the jog run setting terminals are connected (RES-CC ON).
[Parameter setting]
Title
Jog run frequency
f260
Jog run stopping
f261
pattern
Panel jug run mode
f262
[Setting of jog run setting terminal (RES-CC)]
Assign control terminal RES as the jog run setting terminal.
Title
Input terminal selection (RES)
f113
Note 1: During the jog run mode, there is LOW (low speed detection signal) output but no RCH (designated
frequency reach signal) output, and PID control does not work.
Note 2: When the operation panel only is used for operation in jog run mode, the jog run function does not need to
be assigned to any input terminal.
<Examples of jog run>
RES-CC (JOG) ON + F-CC ON: Forward jog run
RES-CC (JOG) ON + R-CC ON: Reverse jog run
( Normal operation frequency signal input + F-CC ON: Forward run
Normal operation frequency signal input + R-CC ON: Reverse run )
Function
f240 -20.0 (Hz)
0: Deceleration stop
1: Coast stop
2: DC braking
0: Invalid
1: Valid
Function
0-203
F-27
Adjustment range
Default setting
Adjustment range
(Jog run mode)
E6581697
6
5.0
0
0
Setting
18

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents