6.9

Jog run mode

: Jog run frequency
: Jog run stopping pattern
: Panel jog run mode
• Function
Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal fenerates a jog
run frequency output at once, irrespective of the designated acceleration time.
Also, you can choose an operation panel start/stop mode between the ordinary start/stop mode and the
jog run start/stop mode.
The jog run function needs to be assigned to an input terminal. When assigning it to the RES terminal, set
to
.
The motor can be operated in jog mode while the jog run setting terminals are connected (RES-CC ON). (Setting
to
.)
[Parameter setting]
Title
Jog run frequency
Jog run stopping
pattern
Panel jug run mode
[Setting of jog run setting terminal (RES-CC)]
Assign control terminal RES ([4: reset signal] in default setting) as the jog run setting terminal.
Title
Input terminal selection (RES)
Note 1: During the jog run mode, there is LOW (low speed detection signal) output but no RCH (designated
frequency reach signal) output, and PID control does not work.
Note 2: When the operation panel only is used for operation in jog run mode, the jog run function does not need to
be assigned to any input terminal.
<Examples of jog run>
RES-CC (JOG) ON + F-CC ON: Forward jog run
RES-CC (JOG) ON + R-CC ON: Reverse jog run
( Normal operation frequency signal input + F-CC ON: Forward run
Normal operation frequency signal input + R-CC ON: Reverse run )
Function
0: Slowdown stop
1: Coast stop
2: DC braking
0: Disabled
1: Panel jog run mode enabled
Function
0-65
F-29
Adjustment range
-20.0 (Hz)
Adjustment range
(jog run setting
E6581158
6
Default setting
5.0
0
0
Setting
4
terminal)