ModBus Data Listing
ModBus Coil List
The following tables list the primary coils for the inverter interface to the network. The
table legend is given below.
• Coil Number - The network
• Name - The functional name of the coil
• R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data
• Description - The meaning of each of the states of the coils
More user manuals on
single bit (binary) value.
Coil
Name
Number
0000h
(Reserved)
0001h
Run command
0002h
FW/RV command
0003h
External trip (EXT)
0004h
Trip reset (RS)
0005h
(Reserved)
0006h
(Reserved)
0007h
Intelligent input terminal 1
0008h
Intelligent input terminal 2
0009h
Intelligent input terminal 3
000Ah
Intelligent input terminal 4
000Bh
Intelligent input terminal 5
000Dh
(Not used)
000Eh
Run/Stop status
000Fh
FW/RV status
0010h
Inverter ready
0011h
(Reserved)
0012h
(Reserved)
0013h
(Reserved)
ManualsBase.com
register address offset
for the coil. The coil data is a
List of Coil Numbers
R/W
R
R/W 0...Stop
1...Run (enable when A003=03)
R/W 0...RV
1...FW (enable when A003=03)
R/W 0...No trip event
1...Trip occurred
R/W 0...No reset condition
1...Reset
R
R
R/W
0...OFF *1
1...ON
R/W
R/W
R/W
R/W
−
R
0...Stop (corresponds to D003 monitor)
1...Run
R
0...FW
1...RV
R
0...Not ready
1...Ready
R
R
R
B−19