Writing in Holding Registers [10h]:
This function writes data in consecutive holding registers. An example follows:
• Write "3000 seconds" as the first acceleration time 1 (F002) in an inverter having a
slave address "1."
• This example uses change data "300000(493E0h)" to set "3000 seconds" as the data
resolution of the registers "0024h" and "0025h" holding the first acceleration time 1
(F002) is 0.01 second.
Query:
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
Note 1:
Note 2:
When writing in selected holding registers fails, see the exception response.
Example
Field Name
Slave address *1
Function code
Start address (high
order)
Start address (low
order)
Number of holding
registers (high order)
Number of holding
registers (low order)
Byte number *2
Change data 1
(high order)
Change data 1
(low order)
Change data 2
(high order)
Change data 2
(low order)
CRC-16 (high order)
CRC-16 (low order)
Broadcasting is disabled.
This is not the number of
holding registers. Specify the
number of bytes of data to be
changed.
Response:
No.
(Hex)
01
1
Slave address
10
2
Function code
00
3
Start address (high
order)
24
4
Start address (low
order)
00
5
Number of holding
registers (high order)
02
6
Number of holding
registers (low order)
04
7
CRC-16 (high order)
00
8
CRC-16 (low order)
04
93
E0
DC
FD
Example
Field Name
(Hex)
01
10
00
24
00
02
01
C3