Auto-Tuning; Motor Constants - Hitachi P1 Basic Instruction Manual

Detroit hoist program v27+
Hide thumbs Also See for P1:
Table of Contents

Advertisement

AUTO-TUNING

Field auto-tuning is generally not required. The VFD will be configured from the factory for the connected motor. If field auto-tuning is
required, please use the step chart below.
NOTE – The E-stop / maximum upper limit will retain function to prevent over-travel into the frame. The VFD will automatically control
the AL relay output for brake release command during auto-tuning.
IMPORTANT!
– If a secondary brake is connected make sure the corresponding terminal function has been assigned to 62:LOG1
before starting the auto-tune.
Step
Remove all attached loads from the hook. If you plan to do a rotational auto-tune remove the wire rope from the
1
drum.
Navigate to VFD parameter HA-01 and select 01: No Rotation for a static tune or 02: Rotation for a rotational tune.
2
Save the selection
On the VFD press the GREEN RUN button once and the auto-tune process will start. If there is an issue or you wish to
3
stop the auto-tune process, then press the RED STOP/RESET button.
Once the auto-tune process is complete the display with show the results of the R1,R2,L for a static tune or
4
R1,R2,L,IO,J for a rotational tune. The auto-tune data will automatically be applied to the motor constant parameters.
5
The auto-tune process is now complete.

MOTOR CONSTANTS

Function
Motor Capacity
Motor Poles
Motor Voltage
Motor FLA
Motor R1 Constant
Motor R2 Constant
Motor L Constant
Motor Io Constant
Motor J Constant
Instruction
Parameter
Hb102
Hb103
Hb106
Hb108
Hb110
Hb112
Hb114
Hb116
Hb118
Page 33
Example Value
Motor in kW
(7.50) kW
01: 4 pole motor
230V / 460V
14.0 A
0.459108 ohms
0.502048 ohms
8.316144 mH
6.11 A
0.03176 kgm2