WAGO-TO-PASS® 761
761-314 TO-PASS® Mobile, 4 AI
Pos : 37.24 /Serie 761 (T O-PASS)/Bedienen/Bedi enen 761-11x/- 21x/-31x Fer nwirken SMS C I veränder n @ 13\mod_1352724545307_21.doc x @ 105910 @ 4 @ 1
8.2.1.2
Changing the Counter Value or Status
To change the value or the status of a counter, send an SMS containing the text
"Counter" and the corresponding control commands (more than one can be sent)
to the TO-PASS
The control commands identify the counter input and the actual command.
Table 41: Control commands for counters
Control command
Cx= (x: 1 ... 4)
E
D
R
n (e.g., 500)
Control commands must be concluded with a semicolon (";").
The TO-PASS
containing the identifier and the transmitted text.
Example:
To activate Counter 2 and set it to 500, and to also deactivate Counter 3, send an
SMS containing the text "Counter: C2=E C2=500 C3=D;" to the TO-PASS
telecontrol module.
The TO-PASS
containing the identifier and the text "COUNTER: OK!".
Pos : 37.25 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 2.0.0
®
telecontrol module.
Function
Select counter 1 ... 4
Activate counter
Deactivate counter
Reset counter
Set counter value
®
telecontrol module acknowledges the command with an SMS
®
telecontrol module acknowledges the command with an SMS
Operation
83
®