Changing The Counter Value Or Status; Table 47: Control Commands For Counters - WAGO -TO-PASS 761 Manual

Telecontrol module compact, 8 ai, web, telecontrol module for fault detection/indication, monitoring and remote control
Hide thumbs Also See for WAGO-TO-PASS 761:
Table of Contents

Advertisement

WAGO-TO-PASS® 761
761-217 Telecontrol Module Compact, 8 AI, Web, MODBUS485
8.2.1.3

Changing the Counter Value or Status

To change the value or the status of a counter, send an SMS containing the text
"Counter" and the corresponding control commands (more than one can be sent)
to the TO-PASS
The control commands identify the counter input and the actual command.

Table 47: Control commands for counters

Control command
Cx= (x: 1 ... 4)
E
D
R
n (e.g., 500)
Control commands must be concluded with a semicolon (";").
The TO-PASS
containing the identifier and the transmitted text.
Example:
To activate Counter 2 and set it to 500, and to also deactivate Counter 3, send an
SMS containing the text "Counter: C2=E C2=500 C3=D;" to the TO-PASS
telecontrol module.
The TO-PASS
containing the identifier and the text "COUNTER: OK!".
Manual
Version 1.0.0
®
telecontrol module.
Function
Select counter 1 ... 4
Activate counter
Deactivate counter
Reset counter
Set counter value
®
telecontrol module acknowledges the command with an SMS
®
telecontrol module acknowledges the command with an SMS
Operation
97
®

Advertisement

Table of Contents
loading

This manual is also suitable for:

761-217

Table of Contents