Advertisement

WAGO-I/O-SYSTEM 750
750-632 Proportional Valve Module

5.3.6.1.2 Hold Current Value ("Freeze")

Figure 16: Hold Current Value ("Freeze")

Table 30: Hold Current Value ("Freeze")

No.
Event
1
Set SPL_EN to "1"
Change setpoint value
2
3
Set DI to "1".
Set SPL_EN to "0"
4
5
Set SPL_EN to "1"
Change setpoint value
6
7
Set SPL_EN to "0"
Set SPL_EN to "1"
8
Move valve via JOG mode!
If "SPL_EN" = 0, the I/O module is in JOG mode. The valve can now be moved
via JOG mode!
Manual
Version 1.3.0, valid from FW/HW-Version 01/01
Description/Behavior
"Automatic mode" is activated.
Ramp starts.
Rising ramp stops. The actual value is frozen.
The actual value is still frozen.
Setpoint value > actual value. The setpoint
value cannot be approached.
Set setpoint value < actual value.
The actual value is still frozen.
Falling ramp starts. The current value is
reduced.