Http Response; Table 55: Setpoint Settings - WAGO 761-114 Manual

Telecontrol module compact, 2 ai, web, modbus485 for wago-to-pass 761, telecontrol module for fault detection/indication, monitoring and remote control
Table of Contents

Advertisement

WAGO-TO-PASS® 761
761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485
10.4

HTTP Response

The response to the request contains a string and, optionally, the time of the Web
portal.
The Web portal time adjusts the time of the WAGO TO-PASS
module.
The data string must contain the following text:
"Values stored" or "Values stored:YY/MM/DD,hh:mm:ss".
Date and time are optional and are required only if the time of the WAGO TO-
®
PASS
telecontrol module is to be set via the Web portal.
The Web portal can also report that the data has not been accepted, or that the
indicated script version is not supported:
"Values not stored"
Starting from Firmware Version 02.33.08, setpoint settings for digital and analog
outputs and for changing the counters can be transmitted as replies.

Table 55: Setpoint settings

Variable Contents
?AO1
&AOn
&DOn
&CEn
&CRn
&CVn
Only those outputs that are available and that are configured for the Web outputs
are evaluated. A check should be made for inbound data sets to determine which
inputs have been configured as counters. There is no reply indicating whether the
counter setting and switching of the outputs has been successful. The subsequent
data transfer would have to be evaluated to determine this (e.g., by a feedback
loop to an input with additional alarm generation).
Manual
Version 1.0.0
1. analog output
n. analog output (n: 2)
n. digital output (n: 1 ... 4)
n. activate counter input (n: 1 ... 4)
n. reset counter input (n: 1 ... 4)
n. change counter value (n: 1 ... 4)
WAGO TO-PASS® Web
®
telecontrol
Format
Normalized value (decimal
places allowed)
0 = not set, 1 = set
0 = active, 1 = inactive
1 = reset
Value[8], hexadecimal
121