Cyclic Data Update Watch Function

The update intervals of cyclic data are monitored. The last output value is held or cleared when the cyclic transmission
stop status continues longer than the set monitoring time.
The cyclic transmission stop status is the status that the D LINK LED is flashing (Data link in operation (cyclic
transmission stopped)) or off (Data link not performed (disconnected)).
Set whether to hold or clear the output value using the output HOLD/CLEAR setting function. For the output
HOLD/CLEAR setting function, refer to the following.
• Output HOLD/CLEAR Setting Function ( Page 184, Section 9.6)
Monitoring starts when cyclic data
are received for the first time.
Master station
Output module
(1) Setting procedure
1.
Set "Method selection" to "Parameter write".
"CC IE Field Configuration" window  Select a main I/O module in "List of stations".  [CC IE Field
Configuration]
 [Online]  [Parameter Processing of Slave Station]
2.
Set the monitoring time in "Cyclic data update watch time setting".
Cyclic data update watch time setting
● Set the greater value for the cyclic data update watch time setting than that of the link scan time.
● While the synchronous communication mode is enabled, the setting of Cyclic data update watch time setting is ignored.
Cyclic data
The cyclic data are updated within
the data link update time.
Item
When the cyclic data update interval
exceeds the set time, the output falls
into the HOLD/CLEAR status.
Cyclic data update time
monitoring time setting
Setting range
• 0 (Not monitor)
• 1 to 20 (0.1 to 2 seconds in units of 100ms)
CHAPTER 9 FUNCTIONS